TECHNICAL SPECIFICATIONS FOR RIPENING CHAMBER COLD ROOM

TECHNICAL SPECIFICATIONS FOR RIPENING CHAMBER COLD ROOM

TECHNICAL SPECIFICATIONS

In this proposal, we have considered supply of the below mentioned room:-

1.) Ripening Cum Cold Room – 8.5 Feet (W ) X 8.5 Feet (L) X 9 Feet (H)

We have considered pre-fabricated PUF insulated panels for wall, ceiling & floor. Freon-based independent split refrigeration systems have been provided. All civil & structural works including finished floor, secondary roofing, etc. shall be in the scope of customer / other agencies.

General Specifications

The room shall be constructed using Prefabricated Rigid Polyurethane Foam (RPUF) insulated panels laminated with Pre-Painted Galvanized Steel (PPGS) lamination on the outside and the inside with serrations for the walls & ceiling. The lamination color shall be RAL 9002 half white. The wall to wall & ceiling to ceiling shall have profiled edges and the joinery shall be with cam-lock arrangement. The wall to ceiling joinery shall be held using flashing from inside & outside. All the resulting panel joinery shall be applied with silicon sealant.

The floor insulation shall be constructed using RPUF insulated panels laminated with 250-micron thick polythene sheet lamination acting as vapor barrier on both sides. Final floor finish above the insulated floor like PCC etc shall be under taken by the end user.

The door shall be Swing type with lamination same as that of wall panels. Door shall be provided with internal safety release mechanism so that people when accidentally locked inside can come out even when the door is locked from outside.

The refrigeration system shall be split type of suitable capacity with Air Cooled Condensing Units located outside the room and the Evaporator Units located inside the room. The condensing unit shall house suitable capacity hermetic compressor, & condenser coil with fans. Electrical starter panel for the full unit shall be mounted inside the condensing unit. The evaporator shall be ceiling suspended type & cabin shall be constructed using GI casing. All the refrigerant tubes shall be with copper construction & Al fins. The evaporator shall be provided with suitable fin spacing to allow sufficient frost to build up to enable longer operation hrs between defrost. The compressor on/off based on the load shall be controlled by a microprocessor based digital temperature controller which shall also control the defrost cycle, on/off of fans, fault indications etc, thereby controlling the entire refrigeration system.


PROPOSAL AND BASIS OF DESIGN WITH SPECIFICATIONS

Based on the input provided for your requirement and with certain assumptions, we propose our solutions as here under

1.

Cold Room Cum Ripening Room

Sl No

Parameter

Cold Room

1

Ambient Temperature [in °C]

 42 deg C

2

Designed Room Temperature [°C]

+ 5 to + 25 Degree C

3

Product to be Stored

Fruits and Vegetables

4

Room Size

8.5 x 9 x 8.5 feet

5

Material of Insulation

RPUF

6

Thickness of Insulation [mm]

60 mm for Walls and Ceiling

7

Wall Lamination In/Out

PPGS/PPGS

8

Ceiling [In/Out]

PPGS/PPGS

9

Serration on panel

Yes

10

Type of floor insulation

RPUF with polythene sheet as vapor barrier

11

Thickness of Floor insulation [mm]

60 mm

12

Size of Door

900 x 2000 mm,1 No.

13

Type of Door

Single Leaf Swing Door, Face-Mounted, 60mm thick, PPGS finish

14

Type of refrigeration system

Split Type

15

Type of Cooling

DX Type

16

Capacity of Refrigeration system/Room  [kW]

8kW  at 17 Degree C

17

Type of Refrigerant

R407C

18

Type of Compressor

Hermetic

19

Type of Condenser

Air Cooled

20

Model of Condensing Unit

hCAHP1508X

21

No of Condensing Units

1 No.

22

Model of Evaporator unit

GEUP08ZT

23

No of Evaporator Units

1 No.

24

Electrical Panel for Ref System

Inbuilt in condensing unit

25

Type of evaporator units

Forced Air Cooled

26

MOC for evaporator units

GI Casing

27

Temperature / humidity indicator-cum-controller

Micro-Processor based

28

Power Supply

415 V, 50 Hz, 3

Ph

29

Type of Humidification

Ultrasonic Humidifier, Mist type

30

Humidification Load

3Kg/hr

31

Ethylene Application System

Liquid type

32

Sensors

Temperature sensor, Relative Humidity sensor, CO2 Level Sensor, Ethylene level sensor, Oxygen Analyzer (0 – 30% )

33

Control System

PLC Based with Data logging

 

 

 

  EXCLUSIONS

 1. Safe storage of the panels, equipment’s & erection material. Crane / MHE for installation and internal shifting of material.

 2.  Any civil & structural works, secondary roofing, shall be in the scope of customer / other agencies’.

 3. Platform for equipment’s to be mounted out door.

 4. Incoming power factor corrected power to the main electrical panel to all out door units in case of freon systems. PLC Controls extra. Earthing with earth pits and lightening arrestor excluded.

 5. Condensate Drain connection to drain point. We have considered piping to the nearest floor level.

 6. Single phase 415V, 50 Hz 32 A power supply for installation activity.

 7. Adequate lighting arrangement for installation activities.

 8. Provision of lights other than inside the rooms mentioned in the design.

 9. Inter connecting piping & cabling has been calculated based on the assumption as mentioned in the design. Additional distance will be charged on RMT basis.

 10.  Any other items other than specified in our bill of quantities and scope of work.

 

Rahul “Nitin”Gupta (BE Civil Engineering ,PMP,MBA Project Management ) is Project Director of this organization he have 8 years of experience in construction industry .He is experts in Site execution, planning , billing department ,Technical advisor .